Technical data
11.4 Derating factors
3VL IEC molded case circuit breakers
148 System Manual, 11/2013, 110 0110 - 02 DS 03
Response values for minimum and maximum settings on the thermal release
Table 11- 22 Setting values I
r
dependent on the ambient temperature (0 °C … 35 °C)
Tripping values for minimum and maximum settings on the
thermal release
VL160X
VL160
VL250 200 216 250 205 240 194 230 182 220 177 215
VL400
VL630
* For TMTUs with fixed setting, the value for "max" applies.
The I
r
of a VL 160X with adjustable TMTU and I
n
= 63 A refers to 50 °C and can be adjusted
there in the range 50 A … 63 A. At an ambient temperature of 30 °C, these values change
so that the adjustable range for Ir is 57 A … 68 A.