Functions
4.1 Protection functions
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
39
Order No.
supplement
Releases
Setting options
L
S
1)
I
1)
G
Overload
protection
Short-circuit protection
(short-time delayed)
Short-circuit
protection
(instantaneous)
Ground-fault protection
I
r
= x I
n
I
sd
= x Ir
t
sd
[s]
I
i
= x I
n
I
g
= I
n
t
g
[s]
LE
ETU20
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
TE
ETU20
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
NE
ETU20
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
TF
ETU20
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
NF
ETU20
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
LF
ETU20
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
SG
ETU22
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
0.6 ... 1, OFF
0,10,3
MG
ETU22
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
0.6 ... 1, OFF
0,10,3
SH
ETU22
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
0.6 ... 1, OFF
0,10,3
MH
ETU22
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
0.6 ... 1, OFF
0,10,3
TH
ETU22
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
0.6 ... 1, OFF
0,10,3
NH
ETU22
0,4 ... 1
1,5 ... 10
0 ... 0,5
11
0.6 ... 1, OFF
0,10,3
SS
ETU30M
3)
0,4 ... 1
06.08.2011
MS
ETU30M
3)
0,4 ... 1
06.08.2011
LS
ETU30M
3)
0,4 ... 1
06.08.2011
UP
LCD-ETU40M
3)
0,4 ... 1
1,25 ... 11
UH
LCD-ETU40
0,4 ... 1
1,5 ... 10
0 ... 0,5
1,25 ... 11
UJ LCD-ETU40 0,4 ... 1 1,5 ... 10 0 ... 0,5 1,25 ... 11
UL
LCD-ETU42
0,4 ... 1
1,5 ... 10
0 ... 0,5
1,25 ... 11
0,4 ... 1
0,1 ... 0,5
UM
LCD-ETU42
0,4 ... 1
1,5 ... 10
0 ... 0,5
1,25 ... 11
0,4 ... 1
0,1 ... 0,5
UN
LCD-ETU42
0,4 ... 1
1,5 ... 10
0 ... 0,5
1,25 ... 11
0,4 ... 1
0,1 ... 0,5
1)
Size dependent
2)
TM to I
n
= 630 A
3)
Motor protection to I
n
= 500 A
4)
Fixed
5)
With single-pole load, tripping occurs at 130% of the set instantaneous short-circuit
current.