Application planning
5.9 Use in transfer control system
3VL IEC molded case circuit breakers
72 System Manual, 11/2013, 110 0110 - 02 DS 03
Structure of the transfer control system
Infeeds line 1 (main system) and line 2 (standby system) are connected to the ATC5300.
In case of system disturbances, the ATC5300 activates the 3VL molded case circuit
breakers Q1 and Q2 accordingly
The 3VL molded case circuit breakers must be equipped with the following accessories:
One motorized operating mechanism per molded case circuit breaker
One alarm switch per molded case circuit breaker
Two auxiliary switches 1NO/1NC per molded case circuit breaker