Installing/mounting
6.2 Mounting and safety clearances
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
83
Safety clearances between molded case circuit breakers
Minimum clearance to be maintained between two molded case circuit breakers installed
immediately above one another with different connection methods.
A
Font connection with cable, direct
B
Front connection with cable lug
C
Front connection with flat connecting bar
D
Rear connection with plug-in base or busbar terminals
Insulation
Insulation of busbar
Figure 6-4 Table of different connection types
Table 6- 4 Safety clearances to be maintained between molded case circuit breakers
Molded case circuit
breaker type
VL160X
VL160
VL250
VL400
VL630
VL800
VL1250
VL1600
Switching capacity
N, H
N, H, L
N, H, L
x 690 V
160 mm
200 mm