The main functions in this context are:
The inputs "Cord-operated switch", "Close pushbutton" and "Open pushbutton" are pulse
inputs, which means a positive edge at the input signal triggers a drive command.
With the "Input RC" input the motor can be switched de-energized (for example at a locked
door)
Automatic closing of the door after parameterizable times
With the input "Cord operated switch" the door can be alternatingly opened or closed. A
special drive command (e. g partial opening) can be parameterized for the opening with a
cord operated switch.
Note
Although the RC input is activated, it is possible to move the door using the service buttons.
SIDOOR ATD401W:
For the ATD401W there is a special menu command available for activating the cold storage
functions (see section Navigation structure in the SIDOOR SERVICE TOOL (Page 274) and section
Digital input signals (Page 132)).
When the menu item "FBLOCK con󹪝g. Cold storage mode" is selected, the existing FBLOCK logic
is deleted and the parameterization is preset with the values described in the table below. For
the commissioning of a cold storage door further settings are required. These are described in
the section Operation as cold storage door (Page 110).
Parameter Value Unit Description
FBLOCK cold storage door
p20127 4 - Logic operation input "RC input" with digital input "DI0"
p20129 10 - Logic operation input "Cord-operated switch" with digital input
"DI2"
p20130 13 - Logic operation input "CLOSE switch" with digital input "DI3"
p20131 16 - Logic operation input "OPEN switch" with digital input "DI4"
p20057 512 - Logic operation output "Open" with DCMD drive command "Open"
p20058 528 - Logic operation output "Cord-operated switch open" with DCMD
drive command "Partial opening"
p20059 768 - Logic operation output "Close" with DCMD drive command "Close"
p20060 256 - Logic operation output "Stop" with DCMD drive command "Stop"
p1250 6 s OPEN switch: Automatic closing after 6 seconds
p1251 0 s Cord-operated switch: No automatic closing
p1252 3000 ms Close command remains applied 3 seconds in closed position
FBLOCK Position block
p20061 32 - Switchover to "Speci󹪝c door range of motion"
p2200 0 cm Normal operation: Start position in open direction
p2201 10 cm Normal operation: Width in opening direction
p2202 0 cm Normal operation: Start position in close direction (is not used here)
p2203 0 cm Normal operation: Width in close direction (is not used here)
SIDOOR functions
4.3 Extended functions
ATD4xxW for industrial applications
104 System Manual, 06/2022, A5E51901827B AA