Analog value representation
B
B.1 Analog value representation in the current measurement range 0
to 20 mA
Display / current measuring range 0 to 20 mA
Values Current measuring
range
Ranges Diagnostic message
Dec. Hex. 0 to 20 mA
32512 7F00 >23.518 mA Overow
1
Overow
32511 7EFF 23.518 mA Overrange -
... ... ...
27649 6C01 20.007 mA
27648 6C00 20 mA Nominal range -
... ... ...
614 266 0.4442 mA
613 265 <0.4442 mA Wire break
1
Wire break
... ... ...
1 1 723.4 nA
0 0 0 mA
1
Substitute value 0 and QI = 0 is provided by the F-module. In S7 F/FH systems, the substitute
value is output as congured at the SUBS_V input of the F-channel driver.
F-AI 8xI 2-/4-wire HART HA