The parameter is only relevant when the "HART enabled" parameter is activated.
5.4.5 Diagnostics: missing power supply voltage L+
Denition
Enabling of the diagnostics for missing or insucient supply voltage L+.
This parameter is "activated" by default, cannot be changed and is for display purposes only.
5.4.6 Double-width terminal block
Denition
Species that a double-width terminal block is used in this slot.
This parameter is only active if the module is plugged into an even-numbered slot.
If set to "Yes", it is not possible to congure an additional module on the slot to the right of the
current slot.
When using the terminal blocks with potential distributors, you have to activate the parameter
"Double-width terminal block".
This parameter only aects the conguration in HW Cong.
5.4.7 Smoothing
Denition
Compensates for measured value uctuations.
The individual measured values are smoothed by ltering.
Description
The measured values are smoothed by a digital lter. Smoothing is achieved by the F-I/O module
calculating the moving average from a number of digitalized analog values specied with the
"Smoothing" parameter.
Smoothing can be set in 4 levels (1, 4, 16, 64 conversion cycles). The level determines the
number of analog signals to be used for generating the moving average.
When "1" is set, smoothing is deactivated.