The parameter is only relevant when the "HART enabled" parameter is activated.
5.4.5 Diagnostics: missing power supply voltage L+
De󹪝nition
Enabling of the diagnostics for missing or insu󹪟cient supply voltage L+.
This parameter is "activated" by default, cannot be changed and is for display purposes only.
5.4.6 Double-width terminal block
De󹪝nition
Speci󹪝es that a double-width terminal block is used in this slot.
This parameter is only active if the module is plugged into an even-numbered slot.
If set to "Yes", it is not possible to con󹪝gure an additional module on the slot to the right of the
current slot.
When using the terminal blocks with potential distributors, you have to activate the parameter
"Double-width terminal block".
This parameter only a󹪜ects the con󹪝guration in HW Con󹪝g.
5.4.7 Smoothing
De󹪝nition
Compensates for measured value 󹪞uctuations.
The individual measured values are smoothed by 󹪝ltering.
Description
The measured values are smoothed by a digital 󹪝lter. Smoothing is achieved by the F-I/O module
calculating the moving average from a number of digitalized analog values speci󹪝ed with the
"Smoothing" parameter.
Smoothing can be set in 4 levels (1, 4, 16, 64 conversion cycles). The level determines the
number of analog signals to be used for generating the moving average.
When "1" is set, smoothing is deactivated.
Parameters/address space
5.4 Explanation of the module/channel parameters
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA 29