6.6 Application case 3: SIL3/Cat.4/PLe, 2- or 4-wire transducer, 1oo2
De󹪝nition
In the following, you can 󹪝nd the wiring diagram and the con󹪝guration of the I/O module F-AI
8xI 2-/4-wire HART HA for application case 3:
SIL3/Cat.4/PLe
1oo2 evaluation
Application for a two-channel or for two single-channel quali󹪝ed sensors
You can 󹪝nd possible diagnostic messages, their causes and remedies in the "Diagnostic
messages" section.
Wiring
You perform the wiring on the appropriate terminal block. You can 󹪝nd more information on this
in the section "Terminal assignment (Page 17)".
Sensor supply
The sensor supply can be powered internally (2‑wire transmitter) or externally (4‑wire
transmitter).
Wiring scheme
Please note application case 1 or 2.
One of these application cases is set up in pairs.
It is recommended to pair the following inputs for the 1oo2 evaluation in the CPU:
Channel 0 and 4
Channel 1 and 5
Channel 2 and 6
Channel 3 and 7
You can combine the channels for the 1oo2 evaluation in the CPU as you like. However, the
mentioned combinations represent the most favorable channel pairings, because these channel
pairs are read in simultaneously by the F-module and therefore you can set the lowest possible
discrepancy time.
In the following 󹪝gure, application case 1 and channels 0 and 4 have been selected as an
example.
Applications of the F-I/O module
6.6 Application case 3: SIL3/Cat.4/PLe, 2- or 4-wire transducer, 1oo2
F-AI 8xI 2-/4-wire HART HA
48 Equipment Manual, 09/2021, A5E50557845-AA