B.3 Analog value representation with deactivated "Wire break
diagnostics" in the current measuring range 4...20 mA
Display / current measuring range with deactivated "Wire break diagnostics" parameter
(current measuring range 4 to 20 mA)
Values Current measuring
range
Ranges Diagnostic message
Dec. Hex. 4 to 20 mA
32512 7F00 >22.814 mA Over󹪞ow
1
Over󹪞ow
32511 7EFF 22.814 mA Overrange
-
... ... ...
27649 6C01 20.0006 mA
27648 6C00 20 mA Nominal range -
... ... ...
1 1 4 mA + 578.7 nA
0 0 4 mA
-1 FFFF 3.9994 mA Underrange
-
... ... ...
-691 FD4F 3.6 mA
-692 FD4C < 3.6 mA
... ... ...
-6144 E800 0.4444 mA
-6145 E7FF < 0.4444 mA Under󹪞ow
1
Under󹪞ow
1
Substitute value 0 and QI = 0 is provided by the F-module. In S7 F/FH systems, the substitute
value is output as con󹪝gured at the SUBS_V input of the F-channel driver.
Analog value representation
B.3 Analog value representation with deactivated "Wire break diagnostics" in the current measuring range
4...20 mA
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA 111