WARNING
Cabling
You must use shielded cables to ensure installation free of interference voltage.
(FAIW-005)
Parameter assignment
Set the following parameters for the corresponding channel:
Parameter Channel with internal sensor supply
Measurement type Current (2-wire transmitter)
Measuring range 4 to 20 mA
Behavior after channel fault Passivate the channel / passivate the entire module
Interference frequency suppression 50 Hz / 60 Hz
HART gate On / O
Diagnostics, Wire break Activated / deactivated
Smoothing 1 / 4 / 16 / 64
HART enabled Activated / deactivated
Number HART message frame repetitions 0 to 10
Diagnostics HART Activated / deactivated
Applications of the F-I/O module
6.2 Application case 1: SIL3/Cat.3/PLd, 2-wire transmitter, 1oo1
F-AI 8xI 2-/4-wire HART HA