Diagnostic interrupt Error code E󹪜ective range
of diagnostic in‐
terrupt
Con󹪝gurable
Internal supply voltage fault 104
H
F-module No
Invalid/inconsistent 󹪝rmware present 11B
H
F-module No
Redundancy partner has di󹪜erent hardware/󹪝rmware version 120
H
F-module No
IO redundancy warning 121
H
F-module No
Diagnostic queue over󹪞ow 13E
H
F-module No
Invalid terminal block 152
H
F-module No
Carrier module or memory in carrier module is defective 154
H
F-module No
Terminal block (TB) or memory in terminal block is defective 155
H
F-module No
Overload or internal sensor supply short-circuit to ground 307
H
Channel No
F-address memory not accessible 30D
H
F-module No
No valid F-address available 30E
H
F-module No
Undertemperature 312
H
F-module No
Internal discrepancy failure 315
H
Channel No
Supply voltage too high 321
H
F-module No
Supply voltage too low 322
H
F-module No
Safety-related HART shuto󹪜 defective 32A
H
F-module No
ADC error 331
H
F-module No
Error in the test circuit 332
H
F-module No
Maintenance messages
The I/O module generates a maintenance message for the following events:
Redundancy partner has di󹪜erent hardware/󹪝rmware version
IO redundancy warning
Carrier module or memory in carrier module is defective
Terminal block (TB) or memory in terminal block is defective
Internal temperature limit reached
Internal malfunction of HART communication detected
In addition, all HART diagnostics are reported as maintenance messages.
You can 󹪝nd more information on this in the section "Maintenance events (Page 72)".
Displays, alarms and messages
7.3 Interrupts
F-AI 8xI 2-/4-wire HART HA
66 Equipment Manual, 09/2021, A5E50557845-AA