Diagnostic message Error
code
Assignment Meaning Remedy
Invalid terminal block 152
H
F-module The terminal block cannot be used with
the current F-module.
Replace the terminal block.
Carrier module or mem‐
ory in carrier module is
defective
154
H
F-module An error of the carrier module or of the
memory module on the carrier module
was detected during operation.
Replace carrier module
Terminal block (TB) or
memory in terminal
block is defective
155
H
F-module An error of the terminal block or the mem‐
ory chip on the terminal block was detec‐
ted during operation.
Replace terminal block
Overload or internal
sensor supply short-cir‐
cuit to ground
307
H
Channel
The internal sensor supply is overloa‐
ded.
Missing or insu󹪟cient supply voltage L
+
Eliminate the short-circuit
in the process wiring.
Check the L+ supply volt‐
age at the terminal block.
Check the terminal block.
F-address memory not
accessible
30D
H
F-module No valid PROFIsafe address is stored in the
retentive memory.
Possible causes:
Initial commissioning
Deliberate parameter change of the
PROFIsafe address
Conformity error between set and ac‐
tual con󹪝guration of the plant
Assign the PROFIsafe ad‐
dress during initial commis‐
sioning or when deliberate‐
ly changing parameters.
Check the consistency be‐
tween the set and actual
con󹪝guration.
No valid F-address avail‐
able
30E
H
F-module F_source_address and F_destination_ad‐
dress parameters invalid
Check F_source_address and
F_destination_address param‐
eters
Undertemperature 312
H
F-module The minimum permissible temperature
was fallen below.
Operate the F-module in the
speci󹪝ed temperature range.
(See section "Technical speci󹪝‐
cations")
After increase of the tempera‐
ture and return to the speci󹪝ed
range, removal and insertion
of the F-module or a POWER
OFF – POWER ON is required.
Internal discrepancy fail‐
ure
315
H
Channel The module has detected an internal er‐
ror.
Possible causes:
Electromagnetic interference is too
high.
Module is defective
If the fault occurs persistently,
replace the F-module.
Supply voltage too high 321
H
F-module The supply voltage is too high. Check the supply voltage.
Supply voltage too low 322
H
F-module The supply voltage is too low. Check the supply voltage.
Safety-related HART
shuto󹪜 defective
32A
H
F-module The F-module has a malfunction in the
safety-related HART shutdown.
Cause:
Error in the F-module
Replace the F-module.
Displays, alarms and messages
7.4 Diagnostic messages
F-AI 8xI 2-/4-wire HART HA
70 Equipment Manual, 09/2021, A5E50557845-AA