"HART gate" parameter
You can use the "HART gate" parameter to switch on the HART function (HART
communication) for the I/O module. The "HART gate" parameter acts as a fail-safe "main
switch" for the complete module.
WARNING
Activation of HART communication
Release the HART communication only if your system is in a state in which a possible
recon󹪝guration of a HART 󹪝eld device is safe.
FAIW-021
WARNING
Impact of a connected HART handheld
Note that the "O󹪜" setting of the "HART gate" parameter is bridged by a connected HART
handheld.
FAIW-020
"HART activated" parameter
You can use the "HART activated" parameter to enable or disable the HART communication
from the a󹪜ected channel of the I/O module to the HART 󹪝eld device.
The parameter is not safety-related, meaning that fail-safe deactivation of the HART
communication is not possible with this parameter.
HART function
8.1 Use
F-AI 8xI 2-/4-wire HART HA
78 Equipment Manual, 09/2021, A5E50557845-AA