Article number 6DL1136-6AA00-0PH1
Protocols
HART protocol Yes
Protocol version
up to Revision 7
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm
Yes
Diagnoses
Monitoring the supply voltage
Yes
Wire-break
Yes
Short-circuit
Yes
Over󹪞ow/under󹪞ow
Yes
Diagnostics indication LED
MAINT LED
Yes; Yellow LED
Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
Channel status display
Yes; green LED
for channel diagnostics
Yes; red LED
for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
between the channels
No
between the channels and backplane bus
Yes
Between the channels and load voltage L+
No
Permissible potential di󹪜erence
between the inputs (UCM) 30 V DC / 25 V AC
Isolation
tested with
between backplane bus and load voltage
1 500 V DC (load voltage L+ and channels I+n bridg‐
ed)
between the backplane bus and functional
ground (FE)
1 500 V DC
between load voltage and functional ground
(FE)
1 500 V DC (load voltage L+ and channels I+n bridg‐
ed)
between the channels and load voltage
370 V AC
between the potential groups of the channels
370 V AC
Standards, approvals, certi󹪝cates
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1
PLd (PLe for 1oo2 voting on the F-CPU)
Category according to ISO 13849-1
cat. 3 (cat. 4 for 1oo2 voting on the F-CPU)
SIL acc. to IEC 61508
Up to SIL 3
Probability of failure (for service life of 20 years
and repair time of 100 hours)
Low demand mode: PFDavg in accord‐
ance with SIL3
< 27E-05 (< 9E-05 for 1oo2 voting on the F-CPU)
Technical speci󹪝cations
9.1 Technical speci󹪝cations
F-AI 8xI 2-/4-wire HART HA
92 Equipment Manual, 09/2021, A5E50557845-AA