Article number 6DL1136-6AA00-0PH1
Protocols
HART protocol Yes
• Protocol version
up to Revision 7
Interrupts/diagnostics/status information
Alarms
• Diagnostic alarm
Yes
Diagnoses
• Monitoring the supply voltage
Yes
• Wire-break
Yes
• Short-circuit
Yes
• Overow/underow
Yes
Diagnostics indication LED
• MAINT LED
Yes; Yellow LED
• Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
• Channel status display
Yes; green LED
• for channel diagnostics
Yes; red LED
• for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
• between the channels
No
• between the channels and backplane bus
Yes
• Between the channels and load voltage L+
No
Permissible potential dierence
between the inputs (UCM) 30 V DC / 25 V AC
Isolation
tested with
• between backplane bus and load voltage
1 500 V DC (load voltage L+ and channels I+n bridg‐
ed)
• between the backplane bus and functional
ground (FE)
1 500 V DC
• between load voltage and functional ground
(FE)
1 500 V DC (load voltage L+ and channels I+n bridg‐
ed)
• between the channels and load voltage
370 V AC
• between the potential groups of the channels
370 V AC
Standards, approvals, certicates
Highest safety class achievable in safety mode
• Performance level according to ISO 13849-1
PLd (PLe for 1oo2 voting on the F-CPU)
• Category according to ISO 13849-1
cat. 3 (cat. 4 for 1oo2 voting on the F-CPU)
• SIL acc. to IEC 61508
Up to SIL 3
Probability of failure (for service life of 20 years
and repair time of 100 hours)
– Low demand mode: PFDavg in accord‐
ance with SIL3
< 27E-05 (< 9E-05 for 1oo2 voting on the F-CPU)
Technical specications
9.1 Technical specications
F-AI 8xI 2-/4-wire HART HA
92 Equipment Manual, 09/2021, A5E50557845-AA