Parameters
6
6.1 Module/channel parameters [ID:151040439051]
Denition
Module/channel parameters are specic parameters whose conguration can aect the entire
module or channels.
Description
The following module/channel parameters are available:
Table 6-1 Parameters and their defaults
Parameter Value range Default Parameter re‐
assignment in
RUN
Eciency range
Diagnostics, Missing supply
voltage L+ (Page22)
• Enabled
• Disabled
Enabled Yes Module
IO redundancy (Page23)
• None
• 2 modules
None No Module
Diagnostics, Short-circuit to
ground (Page23)
• Enabled
• Disabled
Enabled Yes Channel
Diagnostics, Wire break
(Page23)
1
• Enabled
• Disabled
Enabled Yes Channel
Wire-break check (Page23)
• Enabled
• Disabled
Enabled Yes Channel
Channel activated
(Page24)
• Enabled
• Disabled
Enabled Yes Channel
Input delay (Page24)
• None
• 0.05 ms
• 0.1ms
• 0.4ms
• 0.8ms
• 1.6ms
• 3.2ms
• 12.8 ms
• 20ms
3.2ms Yes Channel
DI 16x24VDC PA
Equipment Manual, 06/2023, A5E51654101-AA 21