General technical specifications
6.4 Mechanical and climatic environmental conditions
ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB
73
Testing mechanical environmental conditions
The table below provides information about the type and scope of mechanical environmental
condition tests.
Interface, electronic, and connection modules;
Pneumatic interface modules with FESTO valve terminals
Vibrations Vibration test accord-
ing to IEC 60068-2-6
Type of vibration: Frequency sweeps with a rate of change of
1 octave/minute.
5 Hz ≤ f ≤ 12 Hz, constant amplitude 15 mm
12 Hz ≤ f ≤ 150 Hz, constant acceleration 10 g
Duration of vibration: 10 frequency sweeps per axis in each of three
Shock Shock, tested accord-
ing to IEC 60068-2-27
Type of shock: half-sine
Shock intensity: 30 g peak value, 18 ms duration
Direction of shock: 3 shock tests in +/- direction in each of the
Continuous shock Shock, tested accord-
ing to IEC 60068-29
Type of shock: half-sine
Shock intensity: 25 g peak value, 6 ms duration
Direction of shock: 1000 shock tests in +/- direction at each of the