EasyManua.ls Logo

Siemens SIMATIC MV550 S - Page 91

Siemens SIMATIC MV550 S
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
7.4 Connecting and setting up the reader using the PST
SIMATIC MV500
Operating Instructions, 05/2019, C79000-G8976-C494-02
91
Note that a self-test is performed each time the optical reader is started. The self-test is
indicated by the power LED flashing and lasts from a few seconds to 2 minutes. Once the
test is completed, the power LED lights up in constant green and the optical reader is ready.
Step 3: Configure the Ethernet connection between reader and PC
To configure the Ethernet connection between the reader ("X1 LAN1" interface) and the PC,
follow these steps:
1. Open the Primary Setup Tool with "Start > All Programs > Siemens Automation >
SIMATIC > Primary Setup Tool".
2. In the menu bar under "Settings > Set PG/PC interface..." select the network adapter
through which the reader is connected to the PC and confirm with "OK".
3. Start the network search in the "Network > Search" menu.
4. Click on the "+" character beside the folder symbol in the structure tree and click the entry
"Ind. Ethernet interface".
5. To assign the reader a new IP address, activate the "Assign IP parameters" option.
6. Enter values for the IP address and subnet mask as shown below.
Figure 7-1 Assigning IP address with the PST

Table of Contents

Related product manuals