5 Configuring Communication Connections
A-122
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
Attributes AccessDescription
Max. CMax. Count is the
number of attempted
transmissions including the
first (1-100, default 5).ount
Modifiable
Inactivity Time The inactivity time specifies the interval after which the
connection is terminated if no sign of life is received
from the partner (6-180 s, default 30 s).
Modifiable
Window Time The window time specifies the interval at which sign of
life frames are sent. For SIMATIC NET CPs, the
window time is set to 1/3 of the inactivity time (2-60 s,
default 10 s). Sign of life frames are sent to check the
connection when there is no data traffic.
Display only
Notice
Window Time and Inactivity Time
The partner responds to a sign of life frame with a frame. They are therefore sent
to the partner at the intervals of the window time. To avoid unwanted connection
termination, the inactivity time should be at least three times as long as the
window time.