5 Configuring Communication Connections
A-156
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
“S7 Addressing Mode” Option
When you configure the FETCH ACTIVE / WRITE ACTIVE modes, you can select
the addressing mode. This specifies how the addresses will be interpreted in the
FETCH/WRITE call in the SIMATIC S7 station when accessing DBs:
S7 addressing mode: byte address
S5 addressing mode: word address
This makes it possible for applications to access S5 or S7 stations without needing
to adapt the addresses. This is particularly interesting for existing S5 applications
than can be used unchanged to access S7 stations.
As default, the addressing mode for access to SIMATIC S7 is set (option selected).
System Memory
You can access the following address areas in the system memory on the
SIMATIC S7 PLC using FETCH or WRITE:
Data blocks (DB)
(When accessing DBs, remember that the highest DB number is 255.)
Bit memory (M, MB, MW, MD)
Process image input table (I, IB, IW, ID)
Process image output table (Q, QB, QW, QD)
I/O area inputs (PIW, PID, PIB)
I/O area outputs (PQW, PQD, PQB)
Counters (C)
Timers (T)
Links to Other Systems
The FETCH and WRITE modes supported on ISO transport connections and
ISO-on-TCP or TCP connections can be used with any other device to access the
S7 system memory areas.
To be able to use this type of access, for example for PC applications, you need to
know the PDU structure of the jobs. The required S7 or S5 headers for request
and response frames are 16 bytes long and their structure is described in the
Appendix.

Table of Contents

Other manuals for Siemens SIMATIC NET S7-300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET S7-300 and is the answer not in the manual?

Siemens SIMATIC NET S7-300 Specifications

General IconGeneral
Product Type DesignationSIMATIC NET S7-300
MountingDIN rail mounting
Protection ClassIP20
CPU ModelsVarious models available (e.g., CPU 312, CPU 314)
Communication InterfacesMPI, PROFIBUS DP
Power Supply24 V DC power supply required. Different power supply modules available.
I/O ModulesDigital input modules, digital output modules, analog input modules, analog output modules
ProgrammingSTEP 7 software
Supply Voltage24V DC or 120/230V AC (depending on model)
Digital InputsAvailable via digital input modules
Digital OutputsAvailable via digital output modules
Analog InputsAvailable via analog input modules
Analog OutputsAvailable via analog output modules
Communication FunctionsMPI, PROFIBUS DP, Ethernet (depending on model)
ProtocolsMPI, PROFIBUS DP, TCP/IP (depending on model)
Operating Temperature0°C to 60°C
Storage Temperature70 °C
MemoryDepends on CPU model (e.g., 32 KB to 1.5 MB)

Related product manuals