7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
A-187
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
7.2.3 Status Information (output parameters)
For status evaluation, the following parameters must be evaluated in the user
program:
DONE or NDR
These parameters (DONE with send jobs and NDR with receive jobs) signal
(successful) completion of the job.
ERROR
This indicates that the job could not be executed error-free.
STATUS
This parameter supplies detailed information about the execution of the job.
Status codes can be returned during execution of the job (DONE=0 and
ERROR=0).
Evaluating Status Codes
Remember that the status codes DONE, NDR, ERROR, STATUS are updated at
each block call.
Status Codes during CP Startup
With a complete restart or restart of the Ethernet CP (after activating a switch on
the module), the output parameters of the FC are reset as follows:
DONE = 0
NDR = 0
ERROR = 0
STATUS = 8180
H
for AG_RECV / AG_LRECV or 8181
H
for AG_SEND
/AG_LSEND

Table of Contents

Other manuals for Siemens SIMATIC NET S7-300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET S7-300 and is the answer not in the manual?

Siemens SIMATIC NET S7-300 Specifications

General IconGeneral
Product Type DesignationSIMATIC NET S7-300
MountingDIN rail mounting
Protection ClassIP20
CPU ModelsVarious models available (e.g., CPU 312, CPU 314)
Communication InterfacesMPI, PROFIBUS DP
Power Supply24 V DC power supply required. Different power supply modules available.
I/O ModulesDigital input modules, digital output modules, analog input modules, analog output modules
ProgrammingSTEP 7 software
Supply Voltage24V DC or 120/230V AC (depending on model)
Digital InputsAvailable via digital input modules
Digital OutputsAvailable via digital output modules
Analog InputsAvailable via analog input modules
Analog OutputsAvailable via analog output modules
Communication FunctionsMPI, PROFIBUS DP, Ethernet (depending on model)
ProtocolsMPI, PROFIBUS DP, TCP/IP (depending on model)
Operating Temperature0°C to 60°C
Storage Temperature70 °C
MemoryDepends on CPU model (e.g., 32 KB to 1.5 MB)

Related product manuals