E Linking to Other Systems with FETCH/WRITE
A-307
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
a) Structure of WRITE Frames
The meaning and values of parameters shown without values in the following table
can be found in the section “Parameter Values“.
WRITE request frame WRITE acknowledgment frame
0
System ID
=”S” 0 System ID =”S”
1 =”5” 1 =”5”
2
Length of header
=16d. 2 Length of header =16d.
3
ID OP code
=01 3 ID OP code =01
4
Length OP code
=03 4 Length OP code =03
5
OP code
=03 5 OP code =04
6
ORG field
=03 6 Ack field =0Fh
7
Length ORG field
=08 7 Length ack field =03
8
ORG ID
8 Error field =No
9
DBNR
9 Empty field =FFh
A
Start address
High Byte A Length empty field =07
B Low Byte B
C
Length
High Byte C
D Low Byte D free
E
Empty field
=FFh. E
F
Length empty field
=02 F
Data up to 64 K

Table of Contents