3 Operating the Ethernet CP with
A-85
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
Alternative Procedure
You can also follow the steps outlined below in the SIMATIC Manager:
1. Use the menu command PLC
Display Accessible Nodes to display the
nodes that you can access over Industrial Ethernet.
2. Select the required node in the list displayed.
3. Then select the menu command PLC
Ethernet Address.
Result: The previously selected node is entered directly into the “Addressing”
dialog. You cannot modify the MAC address of the node.
4. Enter the required IP parameters and assign them to the CP (see above under
STEP 5.).
Result:
The CP is now accessible on Industrial Ethernet using the IP address.