Upkeep and maintenance
7.1 Loading new firmware using WBM
Requirement
• The device has an IP address.
• The user is logged in with administrator rights.
Firmware update via HTTP
1. Click "System > Load&Save" in the navigation area. Click the "HTTP" tab.
2. Click the "Upload" button next to "Firmware".
3. Go to the storage location of the firmware file.
4. Click the "Open" button in the dialog. The file is uploaded.
Firmware update via TFTP
1. Click "System > Load&Save" in the navigation area. Click the "TFTP" tab.
2. Enter the IP address of the TFTP server in the "TFTP Server Address" input box.
3. Enter the server port in the "TFTP Server Port" input box.
4. Select the action "Load file" in the "Firmware" table row. Make sure that the file name
is correct.
5. Click the "Set Values" button. The file is uploaded.
Firmware update via SFTP
1. Click "System > Load&Save" in the navigation area. Click the "SFTP" tab.
2. Enter the IP address of the SFTP server in the "SFTP Server Address" input box.
3. Enter the server port in the "SFTP Server Port" input box.
4. Select the action "Load file" in the "Firmware" table row. Make sure that the file name
is correct.
5. Click the "Set Values" button. The file is uploaded.