Upkeep and maintenance
7.1 Loading new firmware using WBM
SCALANCE SC-600
Operating Instructions, 10/2021, C79000-G8976-C453-04
65
4. Connect a PC to the device over the Ethernet interface (P1 - P4).
5. Open a DOS box, change to the directory where the new firmware file is located and
then execute the command "tftp -i <ip address> PUT <firmware>". As an alternative,
you can use a different TFTP client.
If you are not sure that the IP address is correct, you can check this, for example with
SINEC PNI.
If you want to access TFTP in Windows 7, make sure that the corresponding Windows
function is enabled in the operating system.
Result
The firmware is transferred to the device.
Note
Please note that the transfer of the firmware can take several minutes. During the
transmission, the red error LED (F) flashes.
Once the firmware has been transferred completely to the device, the device is restarted
automatically.