Programming
5.1 Programming with STEP 7 (TIA Portal)
Technology module TM FAST (6ES7554-1AA00-0AB0)
Equipment Manual, 04/2023, A5E52301130-AA
33
Parameter
The following table shows the parameters of the instruction.
Parameter Decla-
ration
Data type Default Description
Req
Input
Bool
False
Starts the job at a positive edge.
HWID
1
Input
HW_IO
0
Hardware identifier for module from hardware configuration
Command
Input
UInt
0
Command:
0: Read module status
1: Load TM FAST application from flash memory to FPGA
2: Activate TM FAST application in FPGA
3: Remove TM FAST application from FPGA
4: Delete TM FAST application from flash memory
5: Enable debug interface
6: Disable debug interface
7 to 255: Reserved
FPGAState
Output
Byte
0
FPGA status:
0: No TM FAST application available
1: TM FAST application is loaded but not active
2: TM FAST application is loaded and active
3 to 255: Reserved
ApplicationID
Output
Char array
[1...8]
Application ID of the TM FAST application in the FPGA
UserLogic
Version
Output
LTMFAST_
typeLogic
Version
User logic version in the FPGA, e.g. R01.02.03
Debug
Interface
State
Output
Bool
False
Debug interface status:
0: Debug interface disabled
1: Debug interface enabled
Done
Output
Bool
False
Done = True is displayed for one cycle or until Req is reset: The job
was completed without errors.
Busy
Output
Bool
False
Busy = True: The job has not yet been completed.
Status
Output
Word
16#0
Status of the instruction, displayed for one cycle or until Req is reset:
see "Status parameter" description
Error
Output
Bool
False
Error = True is displayed for one cycle or until Req is reset: An error
has occurred. In this case, Busy and Done are set to False. For de-
tailed information, see Status parameter.
1
Checked at the first call of the instruction and adopted if needed