Parameter data record
B.1 Parameter assignment and structure of the parameter data record
Technology module TM FAST (6ES7554-1AA00-0AB0)
Equipment Manual, 04/2023, A5E52301130-AA
59
Bit
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte ↓
Parameters of the digital inputs DIm
5
Reserved
1
Input delay DI0:
0000B: 0.001 ms
0001B: 0.003 ms
0010B: 0.05 ms
0011B: 0.1 ms
0100B: 0.4 ms
0101B: 0.8 ms
0110B: 1.6 ms
0111B: 3.2 ms
1000B: 12.8 ms
1001B: 20 ms
1010 to 1110B: Invalid
1111
B
: Take over from TM FAST application
(DI_FILTER_USER_VAL_MS system logic parameter)
6
Parameter DI1:
see Byte 5
7
Parameter DIQ2:
see Byte 5
8
Parameter DI3:
see Byte 5
9
Parameter DI4:
see Byte 5
10
Parameter DIQ5:
see Byte 5
11
Parameter DI6:
see Byte 5
12
Parameter DI7:
see Byte 5
13
Parameter DIQ8:
see Byte 5
14
Parameter DI9:
see Byte 5
15
Parameter DI10:
see Byte 5
16
Parameter DIQ11:
see Byte 5