Parameter data record
B.1 Parameter assignment and structure of the parameter data record
Technology module TM FAST (6ES7554-1AA00-0AB0)
60 Equipment Manual, 04/2023, A5E52301130-AA
Bit
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte ↓
Parameters of the RS485/TTL channel CHm
17
Reserved
1
Bus termi-
nating resis-
tor CH0
2.3
Input delay CH0:
0000B: 0.1 µs
0001B: 0.2 µs
0010B: 0.5 µs
0011B: 1 µs
0100B: 2 µs
0101B: 5 µs
0110B: 10 µs
0111B: 20 µs
1000B: 50 µs
1001B: 100 µs
1010B: 200 µs
1011B: 500 µs
1100B: 1000 µs
1101 to 1110B: Invalid
1111
B
: Take over from TM FAST application
(RS485_TTL_FILTER_USER_VAL_MS system logic pa-
rameter)
18
Parameter CH1:
see Byte 17
19
Parameter CH2:
see Byte 17
20
Parameter CH3:
see Byte 17
21
Parameter CH4:
see Byte 17
22
Parameter CH5:
see Byte 17
23
Parameter CH6:
see Byte 17
24
Parameter CH7:
see Byte 17
25...31
Reserved
1
1
Reserved bits must be set to 0.
2
You enable the respective parameter by setting the associated bit to 1.
3
Only permissible for CH0, CH1 and CH4 as well as when system logic parameter RS485_TERMINATION = parameterized