Data Exchange with the SM 335
3-6
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
6ES7 335-7HG00-8BA1
Table 3-2 Meaning of the bits in the SM 335 return code
Bit
Description
7 = 1: SM 335 is in “Measuring Only” or “Comparator” mode
= 0: SM 335 is in “Conditional Cycle” or “Free Cycle” mode
6
1)
= 1: “Measuring Only” mode is activated / was last activated
5
1)
= 1: “Comparator” mode is activated / was last activated
4 = 1: Mode cannot be activated. Reason:
The “Comparator” mode cannot be activated when “Measuring Only” mode
is enabled.
The “Measuring Only” mode cannot be activated when the “Comparator”
mode is enabled or when the “Measuring Only” mode is already active.
3 = 1: The measured value from the analog inputs is not current
(for “Comparator” mode only – with Comparator 2, see Subsection 5.2.1,
Principle of special “Comparator” mode)
2, 1, 0 Error code see Table 3-3
1)
Only bit 5 or 6 can be set but not both
Table 3-3 Description of Bits 0, 1, 2 in the Return Code of the SM 335
Bit2 Bit1 Bit0 Description
0 0 0 No error
0 0 1 Parameter for operating mode ‘Comparator’ faulty
(no analog input designated as comparator input).
0 1 0 Analog input to be used for measuring is disabled.
0 1 1 Error detected at the analog input assigned to the comparator while
‘Comparator’ mode was in force.
1 0 0 Operating mode exited. Reason:
Comparator: Comparator time expired (see Subsection 5.2.2)
Measuring Only (see Section 5.3 ):
Measurement at one analog input: 60 ms expired.
Measurement at 2, 3 or 4 analog inputs: 40 ms expired.
1 0 1 “Comparator” mode exited because new parameters were transferred
via system function to the SM 335.