7.1.5 Commissioning the separately driven fan
The separately driven fan ensures that the main machine is cooled irrespective of the main 
machine speed or direction of rotation. The separately driven fan is only suitable for one 
direction of rotation. 
Checks before the rst test run
Before the rst test run, carry out the following checks:
• The separately driven fan is correctly tted and aligned.
• The rotor runs freely.
• All of the retaining elements and electrical connections are securely tightened.
• The grounding and equipotential bonding connections to the mains have been correctly 
made.
• The air ow is not impeded or shut o by aps, covers or similar.
• If the cooling air is in open circulation, it has only weak, chemically abrasive properties and 
a low dust content.
• All protection measures have been taken to prevent accidental contact with moving or live 
parts.
Performing the test run
1. Switch the separately driven fan motor on and o briey.
2. Compare the direction of rotation of the separately driven fan with the specied direction of 
rotation. The direction of rotation of the separately driven fan is indicated with an arrow on 
the fan cover specifying the direction of rotation or with a terminal designation on the rating 
plate of the separately driven fan unit.
Depending on the version, the fan impeller is visible through the air inlet opening in the fan 
cover on the separately driven fan motor. 
3. If the direction of rotation is wrong, then interchange 2 line cables in the separately driven 
fan motor terminal box.
Note
Use these operating instructions for motors with external fans.