Interfaces
3.6 Power supply
SIMOTION D410-2
54 Manual, 02/2012
3.6 Power supply
The X124 interface is provided for connection of the external power supply.
Note
When using external power supplies (e.g. SITOP), the ground potential must be connected
with the protective ground terminal (PELV).
Interface characteristics
Table 3- 19 Interface X124
Characteristics Type
Connector type Screw terminal 2
Connectable conductor cross-sections
Flexible
With wire-end ferrule without plastic sleeve
With wire-end ferrule with plastic sleeve
0.2 mm² to 2.5 mm²
0.25 mm² to 1 mm²
0.5 mm² to 1 mm²
Stripped length 7 mm
Tool Screwdriver 0.6 x 3.5 mm
Tightening torque 0.5 to 0.6 Nm
Max. current carrying capacity incl. loop-
through
20 A
Max. cable length 10 m
Interface assignment
Table 3- 20 Power supply X124
Representation Terminal Designation
+ Electronic power supply
+ Electronic power supply
M Electronic ground
0
M Electronic ground