X131
Table 4-21 X131 interface assignment
Representation Pin Designation Notes
1 DI/DO 12 High-speed digital I/O 12,
not isolated
2 DI/DO 13 High-speed digital I/O 13,
not isolated
3 M Ground reference of the electronics
1)
4 DI/DO 14 High-speed digital I/O 14,
not isolated
5 DI/DO 15 High-speed digital I/O 15,
not isolated
6 M Ground reference of the electronics
1)
7 AI 0+ Analog voltage or current input
8 AI 0-
1)
Reference potential for the digital inputs/outputs and analog input
NOTICE
Incorrect results of analog-to-digital conversion due to impermissible input voltage
The common mode range must not be violated.
Makes sure that the analog input voltage signals can have a maximum voltage of ±12 V with
respect to the reference potential. If the range is infringed, incorrect results may occur during
analog/digital conversion.
Note
A 24 V supply voltage must be connected to terminal X124 for the digital outputs to be used.
If momentary interruptions in the voltage occur in the 24 V supply, the digital outputs are
deactivated until the interruption has been rectied.
If a digital output (DO 8 … DO 15) is parameterized and the external 24 V power supply is not
connected (or the level is too low), the alarm A03506 will be issued. This alarm can also be
parameterized as a fault.
For further details, see the SINAMICS S120/S150 List Manual, Section List of faults and alarms.
See also
SIMOTION D410-2 DP connection examples (Page 68)
SIMOTION D410-2 DP/PN connection examples (Page 72)
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
SIMOTION D410-2
64 Equipment Manual, 07/2021, A5E33446720B