Commissioning
4.8 Using the AS-i Programmer
Distributed converter for SIMOGEAR geared motors
94 Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
To change an existing address of a slave, the following procedure should be performed:
Plug the AS-i Programmer into the addressing socket of the Inverter
Turn the dial on the Programmer to the ADDR
position. The display
will indicate that this mode has been selected.
button; the screen will display
and the number
of the lower addressed slave.
he existing slave addresses are shown at the bottom of the dis-
Press the and buttons to select the slave address number to be changed.
button; the display now shows
.
The selected number will begin to flash.
and buttons to select the new slave address
button to confirm the new address.
is displayed briefly followed by confirmation of the address