EasyManua.ls Logo

Siemens SINAMICS G120C PN - Electromechanical Components

Siemens SINAMICS G120C PN
478 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.2.3 Electromechanical components
Surge voltage protection circuit
Connect surge voltage protection circuits to the following components:
Coils of contactors
Relays
Solenoid valves
Motor holding brakes
Connect the surge voltage protection circuit directly at the coil.
Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors for
DC-operated coils.
Installing
4.2EMC-compliant setup of the machine or plant
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 45

Table of Contents

Related product manuals