Result
The test is passed if the components required for the specified housing degree of protection are
available.
3.1.3 Electrical cabinet components
Fundamentals
A visual inspection is made to see whether the electrical cabinet components are installed as
defined in the layout diagram and/or circuit diagram.
Test procedure
1. The customer selects electrical cabinet components by random sampling.
2. The selected electrical cabinet components are visually checked to ensure that they are
correctly installed and marked.
Result
The test is passed if the selected electrical cabinet components are installed as specified in the
layout diagram and/or circuit diagram.
3.1.4 Cable installation
Fundamentals
Visual and mechanical checks are made to ensure that cables and conductors have been
installed correctly and are connected correctly according to the circuit diagram.
Test procedure
1. The customer selects cables or conductors by random sampling.
2. The following is inspected:
Are the cables firmly connected?
Have edge protectors been attached to sharp edges?
Are the cables routed according to the circuit diagram?
Result
The inspection is passed if the cable installation does not exhibit any deficiencies and matches
the information in the circuit diagram.
Tests
3.1 Visual inspection
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
N30 N35 N44 N75 M08 U10 Y15
Reference Manual Rev.201902141441 GH180 17