Test procedure
1. The drive is switched on.
2. The drive is switched off and grounded according to the following scheme.
Action Switching states
-Q1 / Q2 -K21 -K22 -K41 -K51
Initial state with the drive switched on off off off on on
Drive off off off off on on
Medium voltage off off off off on on
Wait 600 s off off off on on
Local-remote switch off and actuate Emer‐
gency Off
off off on off on
Connect grounding switches -Q1 / Q2 on on on off on
Open the doors on on on off off
3. The drive is switched off and grounded, the doors are open.
Action Switching states
-Q1 / Q2 -K21 -K22 -K41 -K51
Initial state with the drive switched off on on on off off
Close the doors on on on off on
Open grounding switches -Q1 / Q2 off off on off on
Local-remote switch to "Local" and re‐
lease Emergency Off
off off off on on
Medium voltage on off off off on on
Drive on off off off on on
Result
The test is passed if the corresponding switching states occur.
3.2.19 Failure of a power semiconductor module
Fundamentals
The power section must shut down if a power semiconductor module fails. The failure is
simulated by withdrawing the fiber-optic cable connector from the gating module of a power
semiconductor module. This interrupts the control.
Test procedure
1. The auxiliary voltage is present.
2. The fiber-optic cable connector of a gating module is withdrawn.
A message is displayed on the test station computer.
Tests
3.2 Function test
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
N30 N35 N44 N75 M08 U10 Y15
30 Reference Manual Rev.201902141441 GH180