EasyManua.ls Logo

Siemens SINAMICS PERFECT HARMONY GH180 - Load Test Without Motor; Display Devices in the Cabinet Door

Siemens SINAMICS PERFECT HARMONY GH180
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Test procedure
The test is carried out with reduced power across an inductive load.
1. The drive is switched on.
2. A fiber-optic cable connector of a gating module is withdrawn for each phase.
The corresponding bypass contactor of the failed power semiconductor module energizes.
An alarm message is displayed on the test station computer.
3. The fiber-optic cable connector of an additional gating module is withdrawn.
The inverter is shut down.
A fault message is displayed on the test station computer.
Result
The test is passed if the appropriate messages are displayed on the test station computer.
3.2.26 Load test without motor
Fundamentals
The internal measuring device of the drive is checked for an inductive load. The calibrated
measuring equipment is used as reference.
When testing a version with 60 Hz input transformer on a 50 Hz line supply, the power is
reduced.
Test procedure
1. The drive is switched on in a test mode.
2. The inverter is enabled.
3. The rms values of voltage, current, apparent and active power are measured at the input
and output of the drive.
Result
The test is passed if the values displayed on the test station computer match the reference
values with a tolerance of ±5 %.
3.2.27 Display devices in the cabinet door
Fundamentals
Three display devices are mounted in the cabinet door of the control section. During the "Load
test without motor", a check is made whether the displayed values correspond to the measured
values of the calibrated measuring equipment.
Tests
3.2 Function test
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
N30 N35 N44 N75 M08 U10 Y15
34 Reference Manual Rev.201902141441 GH180

Table of Contents

Other manuals for Siemens SINAMICS PERFECT HARMONY GH180

Related product manuals