3.2.11 Operating state indicator lights
Fundamentals
The operating state indicator lights of the drive are tested.
Test procedure
During the various tests, different operating states arise. The signaling of the following states
is recorded during the test.
Fault (red)
Alarm (yellow)
Drive in Operation (green)
Drive ready (white)
Local operation (white)
Result
The test is passed if the operating state indicator lights light up in accordance with the operating
states.
3.2.12 Digital inputs and outputs for line synchronization
Fundamentals
Digital inputs and outputs are available for the line synchronization; their evaluation and control
is tested using test software.
Test procedure
The function of the inputs and outputs is tested using switches and/or test LEDs.
Input for Up Transfer Request signal
Input for Down Transfer Request signal
Input for Line Contactor Acknowledge signal
Input for VFD Contactor Acknowledge signal
Output for Down Transfer Complete feedback
Output for Up Transfer Complete feedback
Output for Down Transfer Permit feedback
Output for Up Transfer Permit feedback
Output for Line Contactor Unlatch feedback
Tests
3.2 Function test
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
N30 N35 N44 N75 M08 U10 Y15