3.2.7 Phase offset of the output voltage in the three-phase system
Fundamentals
A check is made whether the three phases of the output voltage have a 120° phase offset.
Test procedure
1. The drive is switched on.
2. The output voltages at measuring points VMA, VMB, VMC are displayed on an oscilloscope.
Result
The test is passed if the phase offset is 120°.
3.2.8 Local control via the operator panel
Fundamentals
With the drive in the local mode, a check is made as to whether it can be controlled from the
operator panel.
Test procedure
1. The drive is switched into the local mode using the "Local-remote switch".
2. The following operating states are set and monitored at the operator panel or at the test
station:
Drive on
Drive off
Various points along the U/f characteristic
Reset fault
Emergency Off
Local control priority
Result
The test is passed if the corresponding operating states and specified values occur.
Tests
3.2 Function test
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
N30 N35 N44 N75 M08 U10 Y15
Reference Manual Rev.201902141441 GH180 23