3.2.9 Local control via pushbutton
Fundamentals
With the drive in the local mode, a check is made as to whether it can be controlled using the
pushbutton and potentiometer at the drive.
Test procedure
1. The drive is switched into the local mode using the "Local-Remote switch".
2. The following operating states are set using the operator controls and monitored at the
operator panel or at the test station:
The converter is in the local mode.
Drive on
Drive off
Various points along the U/f characteristic
Reset fault
Result
The test is passed if the corresponding operating states and specified values occur.
3.2.10 Phase offset between output voltage and current with output reactor
Fundamentals
It is tested whether the voltage per phase has a 90° phase offset with respect to the current.
Test procedure
1. The drive is switched on.
2. The phase offset is displayed between the following measuring points using an oscilloscope.
VMA and IFA
VMB and IFB
VMC and IFC
Result
The test is passed if the phase offset is 90°.
Tests
3.2 Function test
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
N30 N35 N44 N75 M08 U10 Y15
24 Reference Manual Rev.201902141441 GH180