Test procedure
1. The "Load test without motor" is carried out
The following values are displayed:
Output current from 0 to +100 %
Output voltage 0 to +100 %
Speed in the range from -100 % up to +100 %
Result
The test is passed if the display device values match the reference values with a tolerance of
±5 %.
See also
Load test without motor (Page 34)
Tests
3.2 Function test