Controlling the safety functions   
5.4 Activating "SBC" via the Safe Brake Adapter 
  Safety Integrated 
96  Function Manual, 08/2023, A5E03264275A 
Table 5- 32  Terminal strip -X15, fast de-energization 
Supply voltage: 230 V AC 
Current consumption: 2 A 
Max. connectable cross-section 2.5 mm
2
 
Spare fuse 
The type of spare fuse is as follows: 2 A, time-lag. 
Note 
Correctly mounting the housing cover after replacing a fuse
 
An adhesive label is provided on the housing cover indicating the position of the connector. 
Mount the cover in the correct position so that the inscription of the label matches the actual 
connectors. 
Mounting 
The Safe Brake Adapter is designed for mounting on a rail according to IEC 60715. 
The dimensions are shown in the following dimension drawing. 
 
Figure 5-11  Dimension drawing of the Safe Brake Adapter (data in mm)