Commissioning
4.3 Quick commissioning
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
31
Parameter Access
level
Function Text menu
(if P8553 = 1)
P0100 = 0 or 2:
(MOT P)
P0307[0] ● 1 Rated motor power [kW / hp]
If P0100 = 0 or 2, motor power unit = [kW]
If P0100 = 1, motor power unit = [hp]
P0100 =1:
(MOT HP)
P0308[0] ● 1 Rated motor power factor (cosφ)
Visible only when P0100 = 0 or 2
(M COS)
P0309[0] ● 1 Rated motor efficiency [%]
Visible only when P0100 = 1
Setting 0 causes internal calculation of value.
(M EFF)
P0310[0] ● 1 Rated motor frequency [Hz]
(M FREQ)
P0311[0] ● 1 Rated motor speed [RPM]
(M RPM)
P1900 2 Select motor data identification
= 0: Disabled
= 2: Identification of all parameters in standstill
(MOT ID)
See also
Parameter list (Page 49)