23
Commissioning
4
NOTICE
For a detailed description of parameter settings for the quick commissioning, refer to the
topic "
Quick commissioning (Page 29)".
4.1 The built-in Basic Operator Panel (BOP)
4.1.1 Introduction to the built-in BOP
OK
OK
M
M
V
V
A
A
Hz
Hz
1/min
1/min
kW
kW
%
%
6723
)DXOW
5XQQLQJ
$872+$1'-2*PRGH
$ODUP
5HYHUVH
581
)81&7,21
83
6WDWXV/('
/&'
GLVSOD\
'2:1
2.
Button functions
Stops the inverter
Single press OFF1 stop reaction: the inverter brings the motor to a standstill in the ramp-
down time set in parameter P1121.
Note:
If configured to be an OFF1 stop, this button is inactive in AUTO mode.
Double press (< 2 s) or
long press ( > 3 s)
OFF2 stop reaction: the inverter allows the motor to coast to a standstill
without using any ramp-down timings.