Commissioning
4.3 Quick commissioning
SINAMICS V20 Inverter
30 Getting Started, 07/2012, A5E03728127
4.3.2 Setting motor data
Functionality
This menu is designed for easy setup of nominal motor nameplate data.
Text menu
If you set P8553 to 1, parameter numbers in this menu are replaced with short text.
Parameter access level
Access level Description Remarks
0 User-defined parameter list Defines a limited set of parameters to which the end
user has access. See P0013 for details on use.
1 Standard Allows access into most frequently used parameters.
2 Extended Allows extended access to more parameters.
3 Expert For expert use only.
4 Service Only for use by authorized service personnel,
password protected.
Setting parameters
NOTICE
In the table below, "●" indicates that the value of this parameter must be entered according
to the rating plate of the motor.
Parameter Access
level
Function Text menu
(if P8553 = 1)
P0100 1 50 / 60 Hz selection
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
(EU - US)
P0304[0] ● 1 Rated motor voltage [V]
Note that the input of rating plate data must correspond with the
wiring of the motor (star / delta)
(MOT V)
P0305[0] ● 1 Rated motor current [A]
Note that the input of rating plate data must correspond with the
wiring of the motor (star / delta)
(MOT A)