Commissioning
4.3 Quick commissioning
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
33
Setting connection macros
M
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1 + DO1- P + N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V
N
)DXOW5XQQLQJ6SHHG
Connection macro settings:
Parameter Description Factory
default
Default for
Cn001
Remarks
P0700[0] Selection of command source 1 1 BOP
P1000[0] Selection of frequency 1 1 BOP MOP
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active
P0771[0] CI: Analog output 21 21 Actual frequency
P0810[0] BI: CDS bit 0 (Hand/Auto) 0 0 Hand mode