Parameter Description Range Factory default Acc. level
1 ON / OFF1 17 Fixed frequency selector bit2
2 ON reverse / OFF1 18 Fixed frequency selector bit3
3 OFF2 - coast to standstill 22 QuickStop Source 1
4 OFF3 - quick ramp-down 23 QuickStop Source 2
9 Fault acknowledge 24 QuickStop Override
10 JOG right 25 DC brake enable
11 JOG left 27 Enable PID
12 Reverse 29 External trip
13 MOP up (increase frequency) 33 Disable additional freq setpoint
14 MOP down (decrease frequency) 99 Enable BICO parameterization
15 Fixed frequency selector bit0
P0702[0...2] Function of digital input 2 0 - 99 0 2
P0703[0...2] Function of digital input 3 0 - 99 9 2
P0704[0...2] Function of digital input 4 0 - 99 15 2
P0712 [0...2] Analog / digital input 1 0 - 99 0 2
P0713[0...2] Analog / digital input 2 0 - 99 0 2
P0717 Connection macro 0 - 255 0 1
r0722.0...12 CO / BO: Digital input values - - 2
P0727[0...2] Selection of 2 / 3-wire method 0 - 3 0 2
0 Siemens (start / dir)
1 2-wire (fwd / rev)
2 3-wire (fwd / rev)
3 3-wire (start / dir)
P0731[0...2] BI: Function of digital output 1 - 52.3 2
P0732[0...2] BI: Function of digital output 2 - 52.7 2
r0752[0...1] Actual analog input [V] or [mA] - - 2
r0754[0...1] Actual analog input value after scaling [%] - - 2
r0755[0...1] CO: Actual analog input after scaling [4000h] - - 2
P0756[0...1] Type of analog input 0 - 4 0 2
0 Unipolar voltage input (0 to +10 V)
1 Unipolar voltage input with monitoring (0 to 10 V)
2 Unipolar current input (0 to 20 mA)
3 Unipolar current input with monitoring (0 to 20 mA)
4 Bipolar voltage input (-10 V to +10 V)
P0757[0...1] Value x1 of analog input scaling -20 - 20 0 2
P0758[0...1] Value y1 of analog input scaling [%] -99999 - 99999 0.0 2
P0759[0...1] Value x2 of analog input scaling -20 - 20 10 2
P0760[0...1] Value y2 of analog input scaling [%] -99999 - 99999 100.0 2
P0761[0...1] Width of analog input deadband 0 - 20 0 2
P0771[0] CI: Analog output - 21[0] 2
P0773[0] Smooth time analog output [ms] 0 - 1000 2 2
r0774[0] Actual analog output value [V] or [mA] - - 2