4 Configuration and Project Engineering
4.1 Parameterizing the SINAMICS V20
SINAMICS V20 at S7-1200/1500 via USS
Entry ID: 109480894, V1.0, 09/2018
20
Siemens AG 2018 All rights reserved
4.1 Parameterizing the SINAMICS V20
Table 4-1: Table for parameterizing the SINAMICS V20 drive
No.
Action
General:
The SINAMICS V20 is parameterized using the built-in BOP. For information on how
to use the BOP, please refer to the SINAMICS V20 Operating Instructions in \10\.
Unless expressly noted, press the and buttons <2s.
1.
Provided that the SINAMICS V20 is in the as-supplied state and the display
displays , continue with no. 2.
If the inverter has already been running, the display menu with the output
frequency is visible on the BOP. In this case, reset the device to factory default.
To do this, use to go from the display menu to the parameter menu and
change the following parameters:
Commissioning parameter P0010 030
(LED on the BOP flashes green.)
Reset to factory setting
5
P0970 21
2.
The display displays and the LED on the BOP has a steady green light.
Use the arrow keys to select the 50/60 or Hz/hp setting that matches your
region and use to exit the screen.
3.
The LED on the BOP flashes green. You are now in the setup menu in the "Motor
data” step and, provided that you are running the example with a connected
motor, you can start entering the motor parameters. When you have finished
entering the motor parameters or if you do not want to enter any motor
parameters, press . You are now in the "Connection macro” step.
4.
Use the arrow keys to choose the connection macro (Cn010) and
use to select it.
5.
Use (>2s) to return to the display menu. The LED on the BOP returns to a
steady green light.
6.
Use to go to the parameter menu and set the user access level to "Expert”:
Access level P0003 3
7.
Set the USS PKW length to 4:
PKW length P2013 4
8.
Transfer the changed parameter values from RAM to EEPROM:
RAM to EEPROM P0971 21
9.
Set the access level back to "Standard”.
Access level P0003 1
10.
Use (>2s) to return to the display menu.
5
When resetting to factory default, connection parameters P2010, P2011, P2023 used for the
USS protocol are not automatically reset in the process. However, they are supplied in step 4 of
the table.