Table A-15 Assigning the Modbus register to the parameters - parameter data
Regis‐
ter
Description Ac‐
cess
Unit Scaling ON/OFF text
or Value range
Data / parameter
Drive identification
40300 Actual power unit code number R - 1 0 … 65535 r0200
40301 Control Unit firmware R - 1 0 … 65535 r0018 / 10000
Drive data
40320 Rated power of the power unit R kW 100 0 … 655.35 r0206
40321 Current limit R/W % 10 0.0 … 6553.5 p0640
40322 Ramp-up time
1)
R/W s 100 10.00 … 655.35 p1120
40323 Ramp-down time
1)
R/W s 100 10.00 … 655.35 p1121
40324 Reference speed
2)
R/W RPM 1 6 … 65535 p2000
Drive diagnostics
40340 Speed setpoint
2)
R RPM 1 -32768 … 32767 r0020
40341 Speed actual value
2)
R RPM 1 -32768 … 32767 r0021
40342 Output frequency R Hz 100 - 327.68 … 327.67 r0024
40343 Output voltage R V 1 0 … 65535 r0025
40344 DC link voltage R V 1 0 … 65535 r0026
40345 Actual current value R A 100 0 … 655.35 r0027
40347 Actual active power R kW 100 0 … 655.35 r0032
40349 Control priority R - 1 HAND AUTO r0807
Fault diagnostics
40400 Failure number, index 0 R - 1 0 … 65535 r0947 [0]
40401 Failure number, index 1 R - 1 0 … 65535 r0947 [1]
40402 Failure number, index 2 R - 1 0 … 65535 r0947 [2]
40403 Fault number, index 3 R - 1 0 … 65535 r0947 [3]
40404 Fault number, index 4 R - 1 0 … 65535 r0947 [4]
40405 Fault number, index 5 R - 1 0 … 65535 r0947 [5]
40406 Fault number, index 6 R - 1 0 … 65535 r0947 [6]
40407 Fault number, index 7 R - 1 0 … 65535 r0947 [7]
40408 Alarm number R - 1 0 … 65535 r2110 [0]
40409 Actual alarm code R - 1 0 … 65535 r2132
40499 PRM ERROR code R - 1 0 … 255 -
Technology controller
3)
40500 Technology controller enable R/W - 1 0 … 1 p2200, r2349.0
40501 Technology controller MOP R/W % 100 -200.0 … 200.0 p2240
Adapt technology controller
3)
40510 Time constant for actual-value filters of
the technology controller
R/W - 100 0.00 … 60.0 p2265
40511 Scaling factor for actual value of the
technology controller
R/W % 100 0.00 … 500.00 p2269
40512 Proportional amplification of the technol‐
ogy controller
R/W - 1000 0.000 … 65.535 p2280
40513 Integral time of the technology controller R/W s 1 0 … 60 p2285