A.1.5.5 Supported objects
Overview
Object class Object name Objects
required
SINAMICS
objects
hex dec
1 hex 1 Identity object x ‑
4 hex 4 Assembly Object x ‑
6 hex 6 Connection Management Object x ‑
32C hex 812 Siemens Drive Object ‑ x
32D hex 813 Siemens Motor Data Object ‑ x
F5 hex 245 TCP/IP Interface Object
1)
x ‑
F6 hex 246 Ethernet Link Object
1)
x ‑
300 hex 768 Stack Diagnostic Object ‑ x
302 hex 770 Adapter Diagnostic Object ‑ x
303 hex 771 Explicit Messages Diagnostic Object ‑ x
304 hex 772 Explicit Message Diagnostic List Object ‑ x
401 hex 1025 Parameter object ‑ x
402 hex ...
43E hex
1026...10
86
Parameter object ‑ x
1)
These objects are part of the Ethernet/IP system management.
For Assembly Object "4 hex" you define the data length. Assembly Object is assigned a cycle
in the control system.
Identity Object, Instance Number: 1 hex
Supported services
Class ● Get Attribute all
● Get Attribute single
Instance ● Get Attribute all
● Get Attribute single
● Reset
Table A-32 Class Attribute
No. Service Type Name
1 get UINT16 Revision
2 get UINT16 Max Instance
3 get UINT16 Num of Instances
Communication
A.1 Communication
Industrial Security
192 Configuration Manual, 08/2017, A5E36912609A