Bit 7 6 5 4 3 2 1 0
Octet Name
6 DS0 (byte 1) 0 0 0 1
5)
0
6)
0
6)
1
6)
1
6)
7 DS0 (Byte 2) 0 0 0 0 0 0 0 0
8 DS0 (byte 3) 0 0 0 0 0 0 0 0
9 Info (byte 1) Mixed = 0x45 (ChannelTypeID = SINAMICS)
10 Info (byte 2) = 24 (number of diagnostic bits/channel)
11 Info (byte 3) = 1 (1 channel signals)
12 Channel Error
Vector
0 0 0 0 0 0 0 Channel 0
1
13 Channel
-related diag‐
nostics
(channel 0)
Err 7 Err 6 Err 5 Err 4 Err 3 Err 2 Err 1 Err 0
14 Err 15 Err 14 Err 13 Err 12 Err 11 Err 10 Err 9 Err 8
15 0 0 0 0 Err 19 Err 18 Err 17 Err 16
1)
Alarm_Specifier
1 ≙ error has occurred and the slot is not OK
2 ≙ error is resolved and the slot is OK
3 ≙ error is resolved and the slot is not okay
2)
Channel fault present
= 1; as long as the drive object has an error condition
3)
Internal fault
= 1; as long as the drive object has an error condition
4)
Module fault
= 1; as long as the drive object has an error condition
5)
Channel information present
= 1; ≙ DS1 exists
6)
Type class of module
= 0011; ≙ Distributed
A.1.2 Communication via PROFIBUS DP
A.1.2.1 General information about PROFIBUS
PROFIBUS is an open international fieldbus standard for a wide range of production and
process automation applications.
The following standards ensure open, multi-vendor systems:
● International standard EN 50170
● International standard IEC 61158
Communication
A.1 Communication
Industrial Security
Configuration Manual, 08/2017, A5E36912609A 113